An Open Letter to the International Association of Fire Chiefs

 

SUBJECT: NFPA 13D Issues to be Debated in Minneapolis

 

An IAFC Member Alert dated May 10, 2002, suggested that IAFC members vote in a particular way on six issues that may be discussed on the floor at the upcoming NFPA meeting in Minneapolis with regard to the proposed 2002 edition of NFPA 13D – Sprinkler Systems for One and Two-Family Dwellings and Manufactured Homes.  The memo twice mentioned the National Fire Sprinkler Association, and attempted to ascribe motives to some of the NFSA positions.  The purpose of this response is to provide IAFC members and others with some additional information on which to base their own decisions on these issues.  The NFSA has a long history of working in cooperation with the IAFC on improved fire protection in general, and residential sprinkler protection in particular.

 

 

The Minimum 0.05 Density Issue

 

This was listed as number 5 in the IAFC memo, but was labeled as the “highest priority” issue.  We would agree that it is the highest priority, since it represents the most fundamental issue with regard to residential sprinklers, namely whether they will effectively control a residential fire. In January of 1999, Factory Mutual called an emergency meeting for the sprinkler industry, and revealed the results of fire tests they had conducted on listed residential sprinklers: many of the recently-listed low-flow sprinklers could not control the same fire test that they had presumably handled at the time of their listing.  This led to a cooperative study by FM, Underwriters Laboratories and the sprinkler manufacturers that found the existing residential fire test, intended to represent a fairly severe corner furniture arrangement, contained a great deal of variability.  An 18-month “recalibration” program took place, involving the development of a new, consistent fire test.

 

Concurrent with that effort, we asked the NFPA Committee on Residential Sprinklers for guidance, and explained that preliminary testing indicated that true equivalency with the corner furniture scenario used as the basis of the residential sprinkler in the late 1970s would lead to a minimum 0.05 gpm/sq ft density.  The Committee made the decision to maintain the severity of the original fire challenge, which in turn has led the laboratories and the sprinkler manufacturers to endorse the absolute minimum of 0.05 gpm/sq ft.  It should be noted that this density represents a substantial reduction from the 1980 edition of NFPA 13D that introduced residential sprinklers.  The minimum flows of 18 gpm for the first sprinkler and 13 gpm for each of two, in combination with the maximum coverage areas of 144 sq. ft., resulted in densities of 0.125 gpm/sq ft and 0.09 gpm/sq ft respectively.  In fact, without the addition of the proposed 0.05 gpm/sq ft. minimum, 13D could be interpreted to still require these higher minimums.  The new minimum represents only about half the minimum allowed for the first generation residential sprinklers, established with the benefit of millions of dollars of federal fire research.  Should we allow even lower?  All test data says no, including fire tests of American sprinklers conducted last year by the Swedish test lab SP and only recently published.  The Swedish tests, involving fires originating in upholstered furniture, showed that densities of 0.05 gpm/sq. ft. showed “reasonably good protection”.  As might be expected, better results were obtained with densities of 0.1 gpm/sq ft., the traditional level for light hazard protection.

 

The fire sprinkler industry is proud of the gains we have made and the economies introduced with lower flow residential sprinklers.  But we believe it would be irresponsible to allow lesser water discharge rates than those being proposed by the Committee. While experience has shown that many of the fires in dwellings take place in kitchens or other areas in which fires which can be controlled with lesser densities, the NFPA 13D Committee decided to maintain the “reasonably worst case” upholstered furniture corner fire as the benchmark fire, and we support that decision.

 

 

Flow Alarm

 

The flow alarm is not intended as an evacuation alarm and we agree that it will therefore not necessarily contribute to life safety in any single fire.  However, experience has shown that it is necessary in order to maintain confidence in 13D systems, which will save lives in the long run.  Communities with residential sprinkler mandates, such as Scottsdale, Arizona and Greenburgh, NY, have found the flow alarm is needed to minimize the potential for water damage in the event of an inadvertent operation of a sprinkler or following successful fire control by sprinklers.

 

 

Elimination of Chapter 5 on Limited Area Systems

 

There is no philosophical or technical issue here, only the recognition that everything that could be done by means of this chapter can be done in other ways. For example, the special allowance for a 7-minute water supply also appears in Chapter 2.  In fact, these “limited area systems” require a minimum flow of 10 gpm for the first sprinkler and 6.5 gpm for each of two, with maximum areas of coverage of 64 sq. ft, meaning that they require minimum densities of 0.16 gpm/sq. ft and 0.10 gpm/sq. ft, more than twice the proposed new minimums discussed above. 

 

 

Listing of Pressure Reducing Valves for Combined Systems

 

Because plumbing codes limit maximum pressures on domestic water systems, pressure reducing valves will be commonly installed on combined sprinkler/domestic systems.  Recognizing that failure of these valves will compromise the sprinkler protection, the Committee is merely seeking to ensure a minimum level of quality and reliability.

 

* * * * *

 

It should be noted that the NFPA Committee on Residential Sprinkler Systems has effectively established consensus on the above issues.  All of these items have gone through public comment and have maintained the support of the Committee as evidenced by successful balloting.  We believe they are sound and do not plan to discuss them on the floor unless they are challenged by some other party.

 

Included in the IAFC memo are two additional issues that the NFSA plans to bring up for floor discussion.  Both of these proposals received the support of the majority of Committee members, but failed to achieve the two-thirds support needed for a successful ballot:

 

 

5 gpm Add-on for Combined Systems

 

Nonmetallic piping for non-combined systems must be listed for fire sprinkler use.  The listing in turn specifies the minimum protection for the piping to ensure that water will reach the sprinklers.  Only for a combined sprinkler/domestic system is non-listed piping allowed to be connected to the sprinklers.  The 5 gpm add-on is intended to account for simultaneous losses that might take place during a fire event.

 

In his negative ballot, IAFC representative Baker noted that the 5 gpm appears arbitrary, and that more study is needed.  The Committee chose this figure because 5 gpm is already used within NFPA 13D as the appropriate simultaneous domestic demand for a two-family dwelling.  Perhaps additional study will lead to a future refinement, but the intent here is to ensure water for the sprinklers as these systems are installed today.

 

 

By-pass for Water Softeners

 

Water softeners and other water treatment equipment are very commonly added to domestic systems by the homeowner.  If this takes place improperly with a combined sprinkler/domestic system, it could compromise the sprinkler protection.  The bypass is a way of ensuring proper sprinkler protection.

 

IAFC representative Baker voted against this issue on the basis of three points: that the Committee does require a redesign of the system if a water softener is added, that there is no evidence of past problems, and that this would add to the cost of the combined system.

We would not expect evidence of past problems inasmuch as the promotion of the combined systems is a new phenomenon.  While we agree there would be a cost impact, we believe it is justified since we have no confidence that the homeowner will undertake the effort to redesign the sprinkler system when the water softener is added.

 

 

* * * * *

 

Costs and Benefits

 

We encourage all IAFC and other NFPA members to review the Report on Proposals and Report on Comments and make up their own minds with regard to the six issues presented above.  In all cases, the NFSA position is the position supported by the majority of Committee members.

 

The IAFC Member Alert appears to oppose anything that would add cost to any NFPA 13D system.  While we respect the goal of low cost for 13D systems, it should not be achieved by low performance.  All standards result in higher costs.  We justify the cost of standards through recognition that the net benefit exceeds the cost.  So the discussion on these six issues should relate to the net benefits of protection.

 

There appears to be special sensitivity to the issues related to combined sprinkler/domestic systems.  These systems can be expected to demonstrate high performance, but only if the appropriate safeguards are in place.  The proponents of one particular type of combined sprinkler/domestic system are viewing the above issues as if they related solely to their particular system, and that is simply not true.  True proponents of residential sprinkler protection need to look at the bigger picture, and not attempt to write the standard around a proprietary product.

 

It is the effectiveness of residential sprinklers that continues to be the number one factor in the continued growth of residential sprinkler protection.  We ask for your help in maintaining that effectiveness.