The Problem
A conflict exists between
the installation standards and the building codes regarding sprinklers
and combustible concealed space separation requirements, specifically in
attics and floor/ceiling assemblies. When conflicts occur, what is actually
required?
Basically NFPA13 requires
sprinklers in combustible concealed spaces, including attics and floor/ceiling
assemblies, other than as excluded by Section 4-13.1 (1996 edition). NFPA13R,
however, in Section 2-6 Exception 4 specifically exempts sprinkler requirements
from attics, penthouse equipment rooms, crawl spaces, floor/ceiling spaces,
elevator shafts, and other concealed spaces that are not used or intended
for living purposes or storage. The building code requires that sprinklers
be installed according to the applicable standard (NFPA 13 or NFPA 13R).
Installing in Accordance
With the Standard
The sprinkler contractor
sprinklered the building according to NFPA 13R but the AHJ then said to
either install attic sprinklers or provide the required draftstopping.
What’s the problem and how can we solve it?
The problem starts with the fact that the model building codes limit the maximum areas of these spaces for both sprinklered and non-sprinklered buildings. This means even when fully sprinklered according to NFPA 13, draftstopping requirements may be required. This results in confusion between the sprinkler and the framing/drywall contractor. What is required and who includes it in their price?
What is Fully Sprinklered?
The building codes provide
basic draftstopping requirements based on the non-sprinklered building.
These requirements limit the combustible concealed spaces to specific sizes
even though the permitted allowable areas can be increased up to 300 percent
with open space and sprinklers. Trade-offs or sprinkler advantages are
permitted for fully sprinklered buildings.
A second problem is related
to confusion over what is considered a fully sprinklered building. Some
codes do not consider 13R as a fully sprinklered building and therefore
do not permit deletion of the draftstopping. They will permit draftstopping
deletions if sprinklers are also installed in the spaces. As an area outside
the dwelling units, however, the attic would need to be protected according
to NFPA 13 even if the balance of the building uses NFPA13R.
What Do The Codes Require?
This publication will provide
a summary of the different code requirements regarding draftstopping and
sprinklers for the model building codes. If in question, it is always better
to consult the AHJ before submitting the bid or final plans for approval.
Find out what is required before you sign the contract.
Example building (used for determining the following code requirements):
Two-story multi-family apartment
building, 8 units per floor, each apartment 800 sq ft. The building footprint
is 82 ft x 87 ft or 7134 sq ft per floor. The building has a center-loaded
corridor serving all units, with two stairways. Construction is unprotected
wood frame. There is an approved 30 ft wide open space along two of the
87 ft sides.
BOCA National Building
Code
R-2 occupancy classification,
multi-family
Sprinkler Requirements: Sprinklers are not required based on occupancy or type of construction.
Allowable area per floor:
Type Construction 5B basic
allowable area non-sprinklered 4,800 sq ft plus street frontage increase
= 7,296 sq ft per floor.
Sprinkler Requirements:
Sprinklers are not required
based on occupancy or type of construction.
Attic Separations:
Draftstopping is required
above and in line with tenant separation walls and on one side of corridor
walls (721.7.2.1) or when area exceeds 3,000 sq ft (721.7.2).
R-2 occupancy classification apartment houses
Sprinkler Requirements: Sprinklers are not required based on occupancy or type of construction.
Allowable area per floor:
Type Construction 5B basic
allowable area non-sprinklered 7,000 sq ft plus street frontage increase
= 8,820 sq ft per floor.
Sprinkler Requirements:
Sprinklers are not required
based on occupancy or type of construction.
Attic Separations
Draftstopping is required
above and in line with tenant separation walls and on one side of corridor
walls and attic space is greater than 3,000 sq ft (716.4.2).
Sprinkler Requirements: Sprinklers are not required based on occupancy or type of construction.
Allowable areas per floor:
Type
VI-UP basic allowable area non-sprinklered 7,000 sq ft
non-sprinklered plus street
frontage increase = 11,760 sq ft allowable areas.
Attic Separations:
Draftstopping is required
above and in line with tenant separation walls and on one side of corridor
walls (2305.2.3).
No exception for sprinklers.
Uniform Building Code:
R Division 1 occupancy classification
hotels and apartment classifications.
Sprinkler Requirements:
Sprinklers are not required
based on occupancy.
Allowable Areas:
Type Construction V-N allowable
area 6,000 sq ft non-sprinklered plus open space increase
= 11,812 sq ft per floor.
Sprinkler Requirements:
Sprinklers are not required
based on occupancy or type of construction.
Attic Separations:
Draftstopping is required
above and in line with tenant separation walls and on one side of corridor
walls and areas greater than 3,000 sq ft, and a maximum separation of 60
ft (708.3.1.2.1).
The model building codes
are currently revising the terminology of draftstopping, firestopping,
smoke barriers, etc. This article uses the single term "draftstopping"
to describe all of the various separation requirements. Consult the specific
building code for actual construction requirements.
Avoid the Problems
To avoid construction delays
and possible increased costs, it is imperative that you apply the codes
correctly. It is not enough to comply only with the installation standard.
Be sure you understand all the requirements and identify errors when you
find them. Check out the plans with the AHJ, do not rely completely on
the plans and specifications.