FM Global and
Factory Mutual Research Revise Fire Protection Guidelines for
K14 Sprinklers
Following New Research Results
(JOHNSTON, RI)
-- New fire protection research by industrial and commercial
property
insurer FM Global and its affiliate Factory Mutual Research has
identified an
uncommon but realistic scenario where K14 Early
Suppression-Fast Response (ESFR) sprinklers, used in some
warehouse
protection
applications, may fail to perform as intended. Specifically, the
findings
revealed certain ignition scenarios can affect the K14 sprinkler's
ability to
suppress a fire in buildings over 40 feet (12.2 m) high.
As a result,
FM Global no longer recommends to its policyholders the use of
K14 sprinklers
as an alternative to in-rack sprinklers in buildings over 40
feet (12.2 m)
high. Rather, the company advises that a combination of
in-rack and
ceiling sprinklers be installed according to FM Global property
loss
prevention engineering guidelines.
The findings
are the result of FM Global's long-range sprinkler technology
research
program. Additional research has revealed that this storage
configuration
issue does not affect K25 ESFR sprinklers installed in 45 foot
(13.7 m) high
buildings nor K14 or K25 sprinklers installed in buildings up
to 40 feet
(12.2 m) high.
This new data
will be reflected in a forthcoming update to FM Global
Property Loss
Prevention Data Sheet 8-9 Storage of Class 1, 2, 3 and 4
Plastic
Commodities.
For additional
installation guidelines on ESFR sprinklers, consult Data
Sheet 2-2,
Installation Guidelines for Early Suppression-Fast Response
Sprinklers. To
order either of these data sheets, visit
www.fmglobal.com/store or call FM Global Customer Services at
781-255-6681.